-1-TECHNICAL MANUALfor CWC CHILLED WATER CASSETTE.This manual provides technical and installation information for CASSETTE 962 series fan coils.INDEX
-10-1 Determine the position for the unit; the air inlet must be at least 400mm from the nearest wall. Also ensure that theposition does not interfere
-11-On plasterboard suspended ceilings, remove sufficient of the ceiling togive clearance for the unit to be fitted, and for access to pipework andele
-12-INSTALLATION of the IMI REMOTE CONTROLLER, (if used).The thermostat should be wired with 7 cores of double insulated 230V cable, 0.5 square millim
-13-Rear Panel AssemblyThe vane on this panel is fixed in position and is not adjustable.1 Fit the filter to the rear panel assembly by dropping the p
-14-CWC WIRING DIAGRAMHeronhill - for all your Airking requirementsTel: 01823 665660www.heronhill.co.ukFax: 01823 665807
-15-CWC CHILLED WATER CASSETTE OPERATING INSTRUCTIONSREMOTE CONTROLLERControls to operate the fan speeds and thermostat are on the front face of the c
-16-User MaintenanceWARNING: The deflector vane on the rear, (air on), panel is fixed in position and does not move.DO NOT ATTEMPT TO ADJUST ITS POSIT
-2-IMI AIR CONDITIONING LIMITED-CASSETTE CEILING MOUNTED CHILLED WATER UNITSPART NUMBERSCASSETTE CWC UNITSModels 8 9 13 19Part Number (without condens
-3-OPTIONAL CONTROL VALVESThe choice of either 2 or 3 way valves are available, these are factory fitted and sited within the valve tray to give thefo
-4-CWC 8 COOLING DUTIESMinimum Speed Medium Speed Maximum SpeedRoom Air On CW Temperature 0.077 m3/s 0.104 m3/s 0.134 m3/sdb /Cwb /CIN /COUT /C Total
-5-CWC 9 COOLING DUTIESMinimum Speed Medium Speed Maximum SpeedRoom Air On CW Temperature 0.098 m3/s 0.122 m3/s 0.165 m3/sdb /Cwb /CIN /COUT /C Total
-6-CWC 13 COOLING DUTIESMinimum Speed Medium Speed Maximum SpeedRoom Air On CW Temperature 0.120 m3/s 0.179 m3/s 0.243 m3/sdb /Cwb /CIN /COUT /C Total
-7-CWC 19 COOLING DUTIESMinimum Speed Medium Speed Maximum SpeedRoom Air On CW Temperature 0.129 m3/s 0.179 m3/s 0.243 m3/sdb /Cwb /CIN /COUT /C Total
-8-WATER VOLUME IN COILS (litres)COIL 8 9 13 19COOLING1.0 1.2 1.6 2.1HEATING0.4 0.5 0.6 0.8OPTIONAL ELECTRIC HEATINGat 230V 50Hz at 240V 50HzCWC (kW)
-9-962 SERIES CWC CASSETTE INSTALLATIONThe 962 SERIES CWC CASSETTE is designed to operate within a suspended false ceiling.The installer supplies:Remo